Installation
24│Page
InanEasy‐Linksystem,thepumpmustbeconnectedtothe“Pumpconnector”in
the“PARENTunit”only.Ifthepumpisconnectedtoanyofthe“CHILDunits”,the
pumpwillnotwork.
PUMPCONTROLCONNECTIONS
Thewaterheatercanbeusedtocontrolarecirculationpump.Properpumpcontrolhelpsto preserve
thelifeofthesystemandsavesenergyaswell.
Thewaterheaterpumpcontrolportisa“normally opendrycontact”,andthereforeneedsadditional
components to properly control a recirculation
pump. To control a recirculation pump, connect the
pump to the “Pump connector” in the water he ater as shown in the diagram below. (In an Easy‐Link
system, connect the pump ONLY to the “PARENT” unit.) The pump is to be connected using suitable
relaysshowninthediagrambelow.
Pleasemakesuretherelaysareproperlyratedfortherecirculationpump.
Usingthewaterheater’sinternalthermistorsasatemperaturecontrol,therecirculationpumpwill only
turnonwhenrecirculationisneeded.
CAUTION
Connecttothis“Pump connector”.
Recirculation
pump
Powersupply
forpump
120VAC
220VACetc
Powersupply
forrelay
ThesecomponentsareNOTincludedwiththewaterheaterand
areexternaltotheunit.Theymustbeacquiredseparately.
Thermal
relay
120VAC
220VACetc
forrelay