The temperature-pressure relief valve must be manually operated at
least once a year. Caution should be taken to ensure that (1) no one
is in front of or around the outlet of the temperature-pressure relief
valve discharge line, and (2) the water manually discharged will not
cause any bodily injury or property damage because the water may
be extremely hot.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
FIGURE 10.
FILLING THE WATER HEATER
Never use this water heater unless it is completely full of water.
To prevent damage to the tank, the tank must be lled with water.
Water must ow from the hot water faucet before turning “ON” gas
to the water heater.
To ll the water heater with water:
1. Close the water heater drain valve by turning the handle to the
right (clockwise). The drain valve is on the lower front of the water
heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when
the water heater is in use.
3. To insure complete lling of the tank, allow air to exit by opening the
nearest hot water faucet. Allow water to run until a constant ow is
obtained. This will let air out of the water heater and the piping.
4. Check all water piping and connections for leaks. Repair as
needed.
VENTING
VENT DAMPERS - Any vent damper, whether it is operated thermally
or otherwise must be removed if its use inhibits proper drafting of
the water heater.
Thermally Operated Vent Dampers: this gas- red water heater
has a thermal ef ciency at or above 80% which may produce a
relatively low ue gas temperature. Such temperatures may not
be high enough to properly open thermally operated vent dampers.
This would cause spillage of the ue gases and may cause carbon
monoxide poisoning.
Vent dampers must bear evidence of certi cation as complying with
the current edition of the American National Standard ANSI Z21.66